undefined
PRODUCTS CENTER
PDR
Meet the PDR series from KEBO, the powerhouse of automatic voltage regulators designed for those who demand robustness and reliability in their power solutions. Whether you're managing a data center, an industrial plant, or a large commercial complex, the PDR series ensures your operations run smoothly without the hiccup of voltage instability.
Category:
AVR/ Three Phase Type
Phone:86-763-5387660
Product Description
| Model | PDR-10KVA | PDR-15KVA | PDR-20KVA | PDR-30KVA | |
| Rated Power | 10000VA/6000W | 15000VA/9000W | 20000VA/12000W | 30000VA/18000W | |
| Technology | Three Phase +Independent Phase + Digital CPU Control Circuit | ||||
| Transformer | Servo Motor Type(Mix Copper & Aluminum) | ||||
| Input | Nominal Voltage | 260-430Vac | |||
| Frequency | 50/60Hz | ||||
| Output | Voltage | 380Vac,±3% | |||
| Respond Time | <1s,against 10% variation ofinput voltage | ||||
| Efficiency | >98% | ||||
| Protection | High Voltage | Output Cutoff by Contactor + Show “H" on Display + Buzzer Beeping | |||
| Low Voltage | Output Cutoff by Contactor+ Show“L"on Display+ Buzzer Beeping | ||||
| Overheat | Output Cutoff by Contactor + Show“CH" on Display+ Buzzer Beeping | ||||
| Overload | Output Cutoff by Contactor + Show“OL" on Display + Buzzer Beeping | ||||
| Phase Failure | Output Cutoff by Contactor+ Show“L"on Display+ Buzzer Beeping | ||||
| Short Circuit | Input Cutoff by Air Breaker | ||||
| Output Delay | 6s/180s Selectable | ||||
| Safety Standard | Insulation Voltage | 2000V/60s | |||
| Insulation Resistance | >5mΩ | ||||
| Cooling | SmartFan(Automatic Startup at 65°C) | ||||
| Certification | CE(LVD+EMC) | ||||
| Operating Environment | Temperature | -5°C~+50°C | |||
| Humidity | 10%~90% non condensing | ||||
| Unit weight/N.w. | 45.0 kgs | 50.0 kgs | 69.0 kgs | 82.0 kgs | |
| Giftbox Size(mm) | 435*395*850 | 435*395*850 | 505*455*830 | 505*455*830 | |
| Carton Size(mm) | 490*450*880 | 490*450*880 | 555*505*880 | 555*505*880 | |